Health Loss Diagrams Insulated Pipes
Heat loss (W/m) diagrams for insulated pipes – ranging 1/2 to 6 inches – insulation thickness 10 – 80 mm – temperature difference 20 – 180 deg C
The heat loss diagrams below is based on metal pipes with fiber glass insulation with thermal conductivity 0.036 W/mK, outdoor condition with moderate wind 9 m/s. A safety factor of 10% is included.
- indoor location – reduce values with 10%
- mineral wool insulation – increase values with 6%
- rigid cellular polyurethane – reduce values by 30%
- Heat loss diagram (W/m)
Pipe Heat Loss – Insulation thickness 80 mm
- 1 W/m = 0.305 W/ft
- 1 oC = 1.8 oF
Pipe Heat Loss – Insulation thickness 50 mm
Pipe Heat Loss – Insulation thickness 40 mm
Pipe Heat Loss – Insulation thickness 30 mm
Pipe Heat Loss – Insulation thickness 25 mm
Pipe Heat Loss – Insulation thickness 20 mm
Pipe Heat Loss – Insulation thickness 10 mm